60HZ Cummins 6CTA8.3-G2 152kW/190kVA Diesel Generator Set

60HZ Cummins 152kW/190kVA Diesel Generator Set
1. Technical Parameter
Parameter Category | Specific Item | Technical Data |
Overall Unit Parameters | Generator Set Model | 6CTA8.3-G2 |
Prime Power (kW/kVA) | 152kW/190kVA | |
Standby Power (kW/kVA) | 167kW/209kVA | |
Rated Frequency | 60Hz | |
Rated Speed | 1800rpm | |
Power Factor | 0.8 (lagging) | |
Fuel Consumption (100% Load) | 44L/H | |
Engine Parameters | Engine Brand | Cummins (Dongfeng Cummins) |
Engine Model | 6CTA8.3-G2 | |
Cylinder Configuration | 6-cylinder, in-line, 4-stroke | |
Aspiration Mode | Turbocharged & After-cooled | |
Bore×Stroke | 114mm×135mm | |
Displacement | 8.3L | |
Compression Ratio | 17.3:1 | |
Fuel System | Bosch In-line Direct Injection Pump | |
Alternator Parameters | Excitation Type | Brushless, Self-excited |
Insulation Class | H Class | |
Protection Grade | IP23 | |
Voltage Regulation Mode | Automatic Voltage Regulation (AVR) | |
Winding Type | Full copper winding | |
Operating Standard | Control System | Cummins PowerCommand® Electronic Control |
Ambient Temperature Range | -20℃ ~ +50℃ | |
Compliance Standard | NFPA 110 Level 1 |
2. Core Product Features
The Cummins 6CTA8.3-G2 152kW/190kVA diesel generator set is a high-performance industrial power supply equipment customized for 60Hz power system scenarios, which integrates Cummins original engine and high-efficiency brushless alternator, and has outstanding advantages in stability, durability and energy-saving performance. As a mainstream medium-power diesel generator set, it is widely recognized in the industrial power supply field for its mature technology and low failure rate.
First of all, this genset is equipped with a genuine Cummins 6CTA8.3-G2 turbocharged and after-cooled engine. The 6-cylinder in-line structure and Bosch in-line fuel injection pump achieve full fuel combustion, effectively reducing energy loss and improving power output efficiency. The 8.3L large displacement design provides strong power reserve, ensuring stable power output even under long-term full-load operation, which perfectly solves the problem of power fluctuation of ordinary generator sets under variable load conditions.
Secondly, the matching brushless self-excited alternator adopts H-class insulation material and IP23 protection grade. Compared with traditional brushed alternators, it has no carbon brush wear failure, lower maintenance cost and longer service life. The full copper winding configuration ensures low heat generation and high conductivity, realizing precise automatic voltage regulation. It can effectively resist voltage and frequency deviation caused by load changes, and the power supply quality fully meets the requirements of industrial precision equipment.
In terms of intelligent control and safety protection, the unit is equipped with Cummins PowerCommand® electronic control system, supporting remote start-stop operation, real-time data monitoring, fault alarm and automatic shutdown protection. It has complete protection functions such as over-speed, over-voltage, under-voltage, over-current and low oil pressure, which can avoid equipment damage caused by abnormal working conditions. The standard integrated radiator cooling system adapts to high-temperature working environment, eliminating the need for complex external heat dissipation configuration and simplifying on-site installation.
In terms of energy consumption and economy, the 100% load fuel consumption is only 44L/H. While maintaining strong power performance, it realizes low fuel consumption operation, greatly reducing the long-term operating cost of enterprises. In addition, the unit has high serialization and versatility of accessories, simple daily maintenance, easy access to spare parts, and low later operation and maintenance threshold, which is very suitable for long-term continuous operation in industrial and commercial scenarios.
3. Main Application Scenarios
This 190kVA Cummins diesel generator set is tailored for 60Hz power supply standard areas and medium-power power demand scenarios. It can be used as both prime power supply and standby emergency power supply, covering multiple fields such as industrial production, commercial construction, infrastructure and special engineering, and is the preferred power equipment for medium-load power guarantee scenarios.
Industrial Production Scenarios: It is widely used in processing factories, manufacturing workshops, mechanical processing plants and other industrial sites. For small and medium-sized industrial enterprises that need long-term stable power supply, the 152kW prime power can meet the continuous power demand of production equipment, mechanical transmission systems and supporting electrical facilities. It can also be used as emergency backup power to avoid production shutdown losses caused by sudden power outages.
Commercial Building & Public Facilities: Applicable to shopping malls, office buildings, hotels, hospitals, schools and other public places. These scenarios have high requirements for power supply continuity. The 167kW standby power of the unit can quickly switch on power in case of municipal power failure, ensuring the normal operation of elevator systems, fire protection facilities, monitoring equipment and basic living electrical equipment of buildings.
Infrastructure & Engineering Construction: It is the ideal temporary power supply equipment for construction sites, road and bridge engineering, municipal construction and field operation projects. Field engineering sites often lack municipal power supply, and the stable output of this Cummins genset can meet the power demand of construction machinery, welding equipment, temporary living electricity and engineering detection equipment, adapting to complex outdoor working environments.
Special Industry & Off-grid Scenarios: It is suitable for remote mountainous areas, pastoral areas, islands and other off-grid power supply areas, as well as communication base stations, water pump stations, mining sites and other special scenarios. The equipment has strong environmental adaptability, can operate stably in high temperature, low temperature and dusty environments, and provides reliable independent power guarantee for unattended field equipment.
4. Core Purpose
The core purpose of Cummins 6CTA8.3-G2 152kW/190kVA 60Hz diesel generator set is to provide stable, reliable and low-cost medium-power power supply guarantee for various industrial and commercial scenarios. It undertakes two core functions of long-term main power supply and emergency standby power supply, and solves the pain points of unstable power supply, insufficient power reserve and high failure rate of traditional generator sets in medium-load scenarios.
In off-grid and power-deficient areas, the unit acts as the main power generation equipment, providing continuous and stable 60Hz standard power supply for production, life and office equipment, ensuring the normal operation of regional economic production and daily life. In areas with complete municipal power supply, it is used as emergency backup power equipment. Once the municipal power fails or power grid fluctuation occurs, the unit can start quickly and switch power supply automatically, avoiding economic losses, safety accidents and equipment damage caused by power interruption.
At the same time, relying on its low fuel consumption, low maintenance and high stability characteristics, this genset effectively reduces the operating cost of enterprise power supply, improves the safety and continuity of industrial production and commercial operation, and is a cost-effective medium-power power supply solution for medium and small enterprises and engineering projects.
5. FAQ
Q1: What is the difference between prime power and standby power of 6CTA8.3-G2 generator set?
Prime power (152kW/190kVA) refers to the long-term continuous usable power of the unit, which supports 24-hour uninterrupted operation and occasional overload operation within the standard range, suitable for long-term power supply as the main power source. Standby power (167kW/209kVA) is the maximum emergency power of the unit, which is only used for short-term power supply in case of municipal power failure or emergency. It cannot operate continuously for a long time, and is mainly used for emergency backup scenarios. In actual use, we recommend configuring load within prime power range to extend the service life of the unit.
Q2: What are the advantages of brushless self-excited alternator of this Cummins genset?
The brushless self-excited alternator equipped with 6CTA8.3-G2 unit cancels the traditional carbon brush and slip ring structure, fundamentally eliminating common faults such as carbon brush wear, poor contact and spark ignition. With H-class ultra-high temperature resistant insulation and IP23 dustproof and waterproof protection grade, it has stronger environmental adaptability. It features stable voltage regulation, low failure rate, no need for frequent replacement of wearing parts, and greatly reduced later maintenance workload and cost. It is more suitable for long-term unattended continuous operation compared with brushed alternators.
Q3: What is the daily maintenance cycle of Cummins 6CTA8.3-G2 diesel generator set?
The daily maintenance of the unit is divided into routine inspection and regular maintenance. Routine inspection needs to check fuel quantity, lubricating oil level, cooling water volume and circuit connection before each startup, and clean the surface dust and sundries after shutdown. The first maintenance is required after 50 hours of operation, including replacing engine oil and filter element. Routine maintenance such as replacing oil filter, fuel filter and air filter is carried out every 250 hours. Comprehensive inspection of turbocharger, cooling system and control system is carried out every 500 hours. Standard maintenance according to the cycle can effectively ensure the power performance of the unit and extend the overall service life.