Good Reputation Supplier 10kv 400v Three Phase Oil Immersed Transformers

Good Reputation Supplier 10kv 400v Three Phase Oil Immersed Transformers

Good Reputation Supplier 10kv 400v Three Phase Oil Immersed Transformers

Main Parameters

Parameter

Specification

Rated power

1,000 kVA reference design; 100–2,500 kVA available

Type

Three-phase, two-winding, oil-immersed distribution transformer

Frequency

50 Hz standard; 60 Hz as a separate design

Primary voltage

10,000 V nominal, Um 12 kV

Taps

±2 × 2.5%, off-circuit, five positions: 10,500 / 10,250 / 10,000 / 9,750 / 9,500 V

Secondary voltage

400 V line-to-line, 230 V line-to-neutral

Vector group

Dyn11 standard; Yyn0 or Dd0 on request

Rated current

≈ 57.7 A on the HV side, ≈ 1,443 A on the LV side

Impedance

4.5% at 75 °C; 4.0–6.0% according to the project's fault level

No-load loss

≈ 1,200 W

Load loss

≈ 9,800 W at 75 °C, full load

Full-load efficiency

≈ 98.9%

Temperature rise

65 K average winding, 60 K top oil; 55 K version for high ambient

Cooling

ONAN; ONAF available on larger ratings

Insulating fluid

Mineral oil to IEC 60296, ≈ 620 kg; ester fluid on request

Core

Grain-oriented silicon steel, three-limb, mitred step-lap joints

Windings

Copper HV layer winding, copper LV foil; aluminium on request

Tank

Welded steel, corrugated wall, hermetically sealed; conservator version available

Insulation level

75 kV lightning impulse, 28 kV power-frequency withstand at Um 12 kV

HV termination

Cable box or porcelain bushings, 12 kV class

LV termination

Cable box or busbar chamber rated for the ≈ 1,440 A secondary current

Tap changer

Off-circuit, five positions, lockable, external handle

Fittings

Pressure relief device, thermometer pocket, drain and filter valves, lifting lugs, jacking pads, earthing terminals

Sound level

≤ 55 dB(A) at 1 m

Mass

≈ 2,600 kg complete; oil ≈ 620 kg

Standards

IEC 60076-1, -2, -3, -5; IEC 60296; GB 1094 / GB/T 6451 equivalent; CE marking on request

Tests

Routine: winding resistance, ratio and vector group, no-load loss and current, load loss and impedance, applied and induced voltage, insulation resistance, oil breakdown, tap changer operation. Type: impulse, temperature rise, sound level

Loss values are design figures. The routine test report that goes out with each unit carries the measured no-load loss, load loss, impedance and ratio for that serial number — and the first thing a serious buyer does is check that the numbers on the report match the ones on the nameplate and on the offer.

Product Description

Ten kilovolts to 400 V is the standard distribution step for plants, buildings and utility LV networks across most of Asia, Europe, Africa and the Middle East. At 1,000 kVA the primary draws about 58 A, so the HV winding is a copper layer winding with graded insulation built to a 75 kV impulse level, which is what the 12 kV class requires. The secondary carries about 1,443 A, which is busbar territory: copper foil winding, a cable box with real gland plates or a busbar chamber, and terminals sized for the current rather than a nominal figure.

The transformer itself is conventional engineering done properly: a four-limb or three-limb grain-oriented core with mitred step-lap joints, no-load loss near 1,200 W, a 4.5% impedance that holds secondary fault current around 32 kA, and five off-circuit taps covering the 9,500–10,500 V band. None of that is exotic. What separates suppliers is whether the copper is actually copper, whether the core is actually grain-oriented, whether the losses on the report are measured or copied, and whether the tank still holds vacuum after a sea voyage.

Mechanically, the tank is corrugated and sealed under vacuum, with expansion taken by the wall, so there is no conservator or breather to service. Where a utility's practice expects a conservator, that version is available, and the choice changes the overall height and the shipping volume — a detail worth settling before the plinth is built rather than after.

Reputation in this trade is built on repeatable details: the same copper weight batch after batch, the same loss level from the first unit to the twentieth, drawings issued before production rather than after, and a serial-numbered test report that a third-party inspector can verify. Buyers who have been burned once usually start asking for exactly those items — and a supplier who has them answers without hesitation.

Core Uses

The unit takes 10 kV down to a 400 V three-phase supply for a plant or a building section. Five uses account for most orders on this ratio.

• Plant incoming supply. One 10 kV connection stepped down to 400 V for the whole low-voltage distribution.

• Motor and process load supply. Pumps, compressors, fans, conveyors and machine lines fed at 400 V.

• Commercial and mixed-use buildings. HVAC, lifts, lighting and tenant distribution from a single transformer.

• Utility LV distribution points. A transformer at the end of a 10 kV feeder serving a residential or mixed cluster.

• Replacement and capacity upgrades. Old units swapped for a low-loss build on the same foundation and cable entries.

Application Scenarios

This ratio fits loads from a few hundred kVA to a couple of MVA where the supply is 10 kV and the distribution is 400 V. The table maps the situations that generate most of our enquiries.

Scenario

Typical load

Why this unit fits

Industrial plants and factories

Motor loads, process lines, plant lighting

10 kV is the common incoming voltage; 400 V matches local motors and panels

Commercial and residential buildings

HVAC, lifts, tenant and dwelling distribution

Compact sealed unit for a basement or plinth; Dyn11 gives 230 V for single-phase circuits

Water treatment and pumping

Pump motors, blowers, controls

Sealed tank and 65 K rise suit unattended stations in hot climates

Utility LV distribution

Residential cluster, shops, street lighting

Standard rating that utilities hold as spares; consistent documentation for asset registers

EPC and export projects

Site distribution, often repeated across a project

Per-unit test reports, witnessed FAT and export packing that survives sea freight

Replacement programmes

Ageing units with rising loss and oil leaks

Same footprint and cable entries, modern loss level, no downstream changes

Where the incoming supply is 20 kV or 35 kV, this is not the right unit whatever the taps say; the insulation class and ratio are both wrong. And where the load is genuinely single-phase, a three-phase transformer is an expensive way to serve it — a single-phase pole mount usually costs less and needs less space.

Product Features

At this rating, features are mostly about verifiability. These are the points a buyer can check before the order, not after.

• Copper windings, stated in writing. Winding material named in the offer and the nameplate, so it can be checked on arrival instead of assumed.

• Measured losses per unit. Around 1,200 W no-load and 9,800 W load loss, with the measured figures on a serial-numbered test report.

• Sealed corrugated tank, vacuum filled. No conservator, no breather, no oil gauge to misread; the conservator version available where utility practice requires it.

• 10 kV class insulation. 75 kV impulse level, graded HV winding, and a 28 kV power-frequency withstand with proper bushing creepage.

• LV termination sized for 1,443 A. Cable box with gland plates or busbar chamber, quoted against the real current.

• Impedance agreed with the fault level. 4.0–6.0% selected per project so breakers and protection settings line up at the first review.

• Documents issued before production. Approved outline and connection drawings, then a test report, oil certificate and packing list per unit.

• Witnessed testing on request. Routine tests per IEC 60076-1 with the buyer's inspector present, and third-party inspection where the project requires it.

Questions Buyers Ask

Question

Answer

How do I verify a supplier's reputation?

Ask for three things: past test reports with matching serial numbers, contactable references on comparable ratings, and a drawing issue process. A supplier who cannot produce the first item is not established, whatever the website says.

What should the test report contain?

Winding resistance, ratio and vector group, no-load loss and current, load loss and impedance, applied and induced voltage, insulation resistance and oil breakdown — all tied to the serial number on the nameplate.

Is 4.5% impedance enough for a 1 MVA unit?

It holds secondary fault current near 32 kA, which ordinary 400 V switchgear can break. If the panel is rated lower, the impedance or the switchgear has to change, and that is agreed before the order rather than after.

Can it run at high ambient or altitude?

Yes, with a different temperature-rise class or a derating. Above 1,000 m cooling performance drops, and a 55 K rise design is usually cheaper than buying the next rating up.

Can two units be paralleled?

Same vector group, ratio, tap position and impedance, with load sharing designed in. A 4.5% unit in parallel with a 6% unit is a common and costly mistake.

What is needed for a quotation?

Rating, voltages, tap range, vector group, impedance or fault level, termination types, cooling, ambient and altitude, quantity and destination port.

Send the single-line diagram and the fault level with the enquiry, and ask for the documentation package in the same email as the price. A supplier who answers both in one reply is the one worth a second order — and in this trade, the second order is what reputation actually means.