Manufacturer Competitive Price and High Quality Single Phase Pole Mounted Transformer 13.8Kv to120V/

Manufacturer Competitive Price and High Quality Single Phase Pole Mounted Transformer 13.8Kv to120V/240V
Main Parameters
Parameter | Specification |
Rated power | 100 kVA reference design; 25–167 kVA available |
Type | Single-phase, two-winding, oil-immersed pole-mounted distribution transformer |
Frequency | 60 Hz standard; 50 Hz as a separate design |
Primary voltage | 13,800 V nominal, 15 kV class |
Taps | ±2 × 2.5%, off-circuit, five positions: 14,490 / 14,145 / 13,800 / 13,455 / 13,110 V |
Secondary voltage | 120/240 V, three-wire, centre-tapped neutral |
Polarity | Additive |
Rated current | ≈ 7.25 A on the HV side; ≈ 417 A at 240 V, ≈ 208 A per 120 V leg |
Impedance | 2.2% at 75 °C; 2.0–2.5% according to the fault level on the spur |
No-load loss | ≈ 200 W, DOE 2016 level |
Load loss | ≈ 1,000 W at 85 °C, full load |
Full-load efficiency | ≈ 98.8% |
Temperature rise | 65 °C average winding rise; 55 °C rise version for hot sites |
Cooling | ONAN |
Insulating fluid | Mineral oil to ASTM D3487 / IEC 60296, ≈ 100 kg; ester fluid on request |
Core | Grain-oriented silicon steel, two-limb, mitred step-lap joints |
Windings | Copper HV layer winding and copper LV sheet standard; aluminium on request |
Tank | Welded steel, corrugated wall, hermetically sealed, pole bracket and lifting lugs |
Insulation level | 95 kV BIL, 34 kV applied potential, 15 kV class |
HV bushing | Porcelain, single bushing with the tank grounded; two-bushing version on request |
LV terminals | Two 120 V legs plus neutral, stud terminals under a bolt-on cover, rated for the ≈ 420 A secondary current |
Protection | Conventional with upstream cutout and arrester, or CSP with internal HV fuse, arrester and secondary breaker |
Fittings | Pressure relief device, drain plug, fill plug, lifting lugs, earthing lug, pole bracket, arrester mounting provision |
Sound level | ≤ 45 dB(A) at 1 m, NEMA test distance |
Mass | ≈ 420 kg complete; oil ≈ 100 kg |
Standards | IEEE C57.12.00, C57.12.20, C57.12.90; DOE 10 CFR 431; IEC 60076-1 reference for export projects |
Tests | Routine: winding resistance, ratio and polarity, no-load loss and current, load loss and impedance, applied and induced voltage, oil breakdown. Type: impulse, temperature rise, sound level |
Loss values are design figures and are the first place a low price gets built in. The routine test report that ships with each unit carries the measured no-load loss, load loss, impedance and ratio for that serial number, and that is the document to compare when two offers differ by ten percent.
Product Description
The secondary is the part that makes this transformer useful. Two 120 V legs with a centre tap give 120 V for lighting and receptacles and 240 V across the outer legs for pumps, dryers, compressors and welders, all from one pole and one service drop. At 100 kVA the 240 V current is about 417 A, so each 120 V leg carries roughly half of that — the figures a service panel and meter are selected against. A 2.2% impedance puts the prospective secondary fault current near 19 kA at 240 V, which is what the service equipment has to withstand and break.
On the primary side, 13.8 kV draws only about 7.25 A. The HV winding is a copper layer winding with graded insulation built to a 95 kV impulse level and a 34 kV applied potential, which is what the 15 kV class requires. A single porcelain bushing with the tank grounded is normal for a radial spur, and the primary is protected upstream at the cutout. In the CSP version, the internal HV fuse, arrester and secondary breaker sit inside the tank, so the pole carries one device instead of four.
The core is a two-limb grain-oriented build with mitred step-lap joints, holding no-load loss near 200 W. That figure matters more than it looks: a pole mount is energised around the clock for a load that may only peak in the evening, so every 100 W of no-load loss is about 876 kWh a year in a 60 Hz system. On a hundred units in a co-op's territory, that is a distribution loss line item, not a rounding error.
The tank is corrugated and sealed, filled under vacuum, with expansion taken by the wall. There is no conservator and no oil gauge to misread, and no gasket maintenance between inspections. Copper windings on both sides carry the 417 A without the hot-spot spread that thin aluminium develops at this current, and the low-side stud terminals are sized for the full secondary current rather than a nominal figure — an undersized terminal block is the most common failure on this kind of unit.
Where price and quality actually separate is here: copper versus aluminium windings, grain-oriented core versus scrap-grade steel, measured losses versus catalogue losses, a sealed tank with proper paint versus a thin coat, and a routine test report per serial number versus a certificate that covers a batch. Two quotations on the same datasheet can differ by thirty percent, and that difference lives in exactly those five items.
Core Uses
The unit steps 13.8 kV down to a three-wire 120/240 V service. Five uses account for most of the orders on this ratio.
• Rural and farm service. House, barn, well pump and shop equipment on one service, with 240 V available for motors and 120 V for lighting.
• Residential clusters on rural lines. Six to ten homes per pole mount, sized on diversified demand rather than connected load.
• Small commercial and workshop loads. A shop, a welding bay, a small compressor or a fuel station on a three-wire service.
• Irrigation and stock water pumping. 240 V single-phase pump motors fed from a 13.8 kV spur where three-phase is not economic.
• Construction and replacement stock. Temporary site power, and the spare that gets a feeder back on after a failure.
Application Scenarios
This unit belongs where the load is single-phase, spread out and moderate, and a 13.8 kV line already runs past the site. The table sets out the situations that generate most enquiries.
Scenario | Typical load | Why this unit fits |
Rural co-op distribution | Farmsteads, scattered homes, small pumps | 13.8 kV is the working voltage on these lines; a pole mount avoids a three-phase extension |
Residential subdivision edge | Six to ten homes at diversified demand | 120/240 V three-wire matches standard service panels and meters |
Farm and irrigation service | House, barn, 240 V well or irrigation pump | 240 V across the outer legs runs single-phase motors without a three-phase service |
Small commercial premises | Shop, welder, compressor, lighting | One service covers both 120 V circuits and 240 V equipment |
Oil and gas lease sites | Pump jack controls, instrumentation, lighting, quarters | CSP option and sealed tank suit unattended sites |
Stock and replacement programmes | Utility spares, storm replacement | Standard rating, 420 kg, set by one line truck; consistent test documentation |
Two limits are worth stating. This transformer cannot supply a three-phase load, and it should not be asked to carry a single 20 kW motor starting direct-on-line — the dip will show on every service on the spur. Size it on diversified demand, and leave the spare capacity for load growth rather than for starting current.
Product Features
What a buyer is really paying for at this rating is durability and honest test data rather than features on a brochure. These are the points worth checking.
• Copper windings as standard. Lower hot-spot temperature and better short-circuit withstand than an aluminium build at the same nameplate rating.
• Measured losses, not catalogue losses. Around 200 W no-load and 1,000 W load loss, DOE 2016 level, with the measured figures on the per-unit test report.
• Sealed corrugated tank. Vacuum filled, no conservator, no breather, no oil gauge — the unit stays closed between inspections.
• 15 kV class insulation. 95 kV BIL, 34 kV applied potential, graded HV winding and a porcelain bushing sized for outdoor creepage.
• 120/240 V three-wire secondary. Centre-tapped neutral with two 120 V legs, terminals sized for 417 A rather than a nominal figure.
• CSP or conventional. Internal fuse, arrester and secondary breaker for a self-protected pole, or a plain unit protected at the cutout.
• Five tap positions. 13,110–14,490 V covers the spread on a long rural feeder without touching a regulator.
• Documented price, documented quality. Nameplate with ratio, impedance and losses, outline drawing with bracket dimensions, and a test report tied to the serial number.
Questions Buyers Ask
Question | Answer |
What drives the price difference between offers? | Winding material, core grade, loss level, tank and paint quality, protection package, and whether a per-unit test report is included. A quote that is thirty percent cheaper usually moved on two or three of those. |
How many homes will 100 kVA serve? | Roughly six to ten at a diversified demand of 5–8 kW per home. Electric heating, heat pumps and EV charging push it toward the lower end. |
What does 120/240 V mean exactly? | Three wires: two 120 V legs and a centre-tapped neutral, giving 240 V across the outer legs. Standard service panels and meters are built around it. |
CSP or conventional? | CSP if the pole should be self-protected with fewer external devices to inspect; conventional if protection sits upstream or the service has its own main breaker. |
Is a 50 Hz version available? | Yes, as a separate design. Core and turns change, so 50 Hz and 60 Hz units cannot be mixed on one order line or swapped on site. |
What is needed for the offer? | Rating, primary voltage and tap range, 120/240 V secondary, CSP or conventional, quantity, altitude and ambient, and the destination port. Standard drawings come back with the price. |
Ask for the measured losses and the serial-numbered test report before comparing prices — those two documents tell you what the transformer will cost to run, which is usually more than the purchase price over its service life. That is what a competitive price should mean.

